Indoor Air Quality in Schools
Oregon Elementary School
During the conditions audit at the Oregon Elementary School three
concerns were identified as targets for possible retrofit work:
- control ventilation based on occupancy as indicated by CO2 sensors
to maintain recommended ventilation and potentially save on heating
cost by reducing periods of over-ventilation
- general maintenance for 27 unit ventilators to increase outside
air to recommended levels while maintaining temperature control
- adding mechanical ventilation for a six classroom portable with
restrooms that were without any mechanical ventilation.
It was anticipated that the energy savings from more efficient
operation of the ventilation provided to the common core of the building
(gym, cafeteria, and auditorium) would offset the added cost of
providing proper ventilation to the classroom areas. Based on available
funding, it was decided to address the first two items.
Maintenance performed by the district to address the unit ventilator
recommendation was completed during the summer of 2003. Unit ventilators
were cleaned, including outside air intakes, and calibrated. Dampers,
controls and valves were checked, adjusted, and replaced as needed.
Ventilation of the gym, cafeteria, and large auditorium was also
improved. The multizone fan system was reconfigured so that these areas
could be operated as isolated zones by the operation of dampers
controlled by CO2 sensors for the cafeteria and auditorium
and an occupancy sensor for the gym. Temperature, relative humidity and
CO2 levels in the cafeteria and auditorium and selected
classrooms were monitored pre and post retrofit. Maintenance on the unit
ventilators in the classrooms produced a significant improvement in
measured flows of outside air provided to each room with average outside
air flows going from 149 cfm pre-retrofit to 356 cfm post-retrofit.
Sixteen out of 20 rooms were adequately ventilated post retrofit versus
only two of 20 pre retrofit. CO2 monitoring also confirmed
improved ventilation rates. Based on an energy audit performed by a
private company as part of the state of Oregon’s SB 1149 program, energy
savings from the multizone fan system retrofit were estimated at 308
MMBtu/year with a dollar savings of $1,997/year. This yields a simple
pay back of 4.5 years for a $9,000 investment. |