Portable Classrooms - Indoor Environment
Cromwall Elementary School, Cromwall, New York
The NY PERC, located at Willow Avenue Middle School in Cornwall, New
York was sited in September 2002. It was built by Design Space Modular,
in McCrae, Georgia and consisted of (2) end-to-end 24’-0” x 36’-0”
classrooms sharing a common wall, corridor and bathroom, totaling 1,724
sq. feet. During testing, each classroom was occupied. The PERCs were
located next to the conventional built relocatable classrooms and was
expected to be 50% more energy efficient and have enhanced lighting
levels. FSEC monitored energy performance in both classrooms. All data
was downloaded daily to FSEC via modem.
Results
Overall Results
Measured data shows that an overall savings of 36%
were achieved for the combined heating and cooling loads. Good data
collection periods were November 17, 2002 – June 20, 2003.
Construction efficiency related differences between the two NY
classrooms are listed in the table below.
|
Side-by-Side Study of NY PERC
Specifications of Standard and Energy Efficient Construction |
| Characteristic |
Standard Relocatable |
PERC |
| Floor Insulation |
R-11 |
R-13 Formaldehyde Free |
| Wall Insulation |
R-11 |
R-19 Formaldehyde Free Insulation with ½” jpolystyrene board |
| Ceiling Insulation |
R-19 |
R-30 @ roof deck, w/airspace between rafters for maintaining
cold roof |
| Windows |
Season Shield Double Glazed |
Low-E Thermopane by Atrium
Note (U=0.24, SHGC – 0.38) |
| Lights |
3,072 Total Installed Wattage |
1,536 Total Installed Wattage |
| Skylights |
None |
12 SunOptics skylights |
| Interior Floor Finish |
26 oz. Rolled carpet |
Non-permeable backing, Interface carpet tile, low VOC glue |
| Heating System |
Board Electric Resistance Heat |
Bard Qtec Heat Pump, HSPF 7.5 |
| Cooling System |
Bard Central Air Conditioning, SEER 10 |
Bard Qtec Central Heat Pump, SEER 12 |
| Ventilation System |
Fixed CFM during occupancy |
CO2 control for ventilation with 3-step fan speed and
energy recovery ventilator Bard CS200 Energy Monitor |
| Bathroom Exhaust Fan |
Broan, 4 sonne |
Broan Ultra Silent Fan, 1.0 sonne |
| HVAC Through Wall Install |
Standard gasket provided with unit-rough opening not addressed |
On site – sealed rough opening at HVAC wall connection with
mastic and fiber tape |
| Duct Joints |
Industry Standard |
Sealed with Mastic (post construction) |
| Building Leakage* |
CFM25out = 3627 |
CFM25out = 3692 |
| Building Leakage* |
ACH50 = 16.37 |
ACH50 = 16.66 |
| *Leakage Testing performed – December 9, 2002 |
Detailed Results
Figure 1 shows a pie chart revealing how energy
was used in the Control portable classroom over the year; Figure 2 shows
the same data for the PERC portable revealing a 36% energy savings. The
clear message of the data is that energy use in portable classrooms is
dominated by heating, cooling and ventilation. Lighting consumption is
very much a secondary issue and other end-uses are virtually
unimportant.

The
graph at right shows the average shape of the energy savings over the
entire school year over a 24 hour cycle from November 2002 – June 20th
of 2003. The measured overall energy savings of the more energy
efficient experimental model was 48 kWh/day or 36%. Most of the savings
were concentrated in the evening and early morning hours when the
heating season was operating at its maximum. Note that the average peak
electrical demand of the experimental unit at 8 AM is more than 2 kW
(20%) lower than the control.
Figure 3 shows how the HVAC savings varied over the winter months.
Savings from November - March averaged 47% even with a difficult to
resolve problem with the control thermostat in the PERC portable. This
occurred when the system would refuse to turn off the HVAC system during
unoccupied periods and would maintain abnormally high temperatures. A
series of trial and error procedures were used to isolate the problem
which eventually turned out to be a thermostat compatibility issue with
the automated (CS-2000) control system. This was only resolved near the
end of the project; savings would be considerably higher in a second
year of monitoring. Regardless, the success in resolving this problem
was reflected in more successful projects in North Carolina and Florida.

Figure 3
Lessons Learned
- In cold, heating dominated climates such as Rochester, New York,
insulation measures and duct air leakage control measures look to be
the most important.
- Results further suggest that ground source heat pumps or natural
gas heating may be attractive alternatives to air-source heat pumps.
- Daylighting, while producing savings in lighting energy, tends to
increase heating budgets and is not as attractive as insulation and
heating system measures. It appears important that a successful
daylighting strategy in 12 such locations utilize highly insulated
glazing (double glazed low-e was assumed) in order to be successful.
- Floor and wall insulation is important.
- Solar control glass is counterproductive.
|